Replacing grounded outlets with grounded metal junction box

The name of the pictureThe name of the pictureThe name of the pictureClash Royale CLAN TAG#URR8PPP












3















Replacing several 3 prong outlets in my 1968 home. Tried searching to find an answer but most questions seem geared towards replacing 2 prong outlets with 3 prong and don't apply here.



My wiring appears to be romex with a bare copper ground wire. After removing the outlet covers and pulling the outlets (all 3 prong) out of their junction boxes, I've found that each has the hot and neutral wires connected to the outlet and the ground wire connected to the junction box. Each outlet has a black screw in the bottom corner which I assume makes contact with the metal box and provides a ground path?



Outlet Example



What is the correct way to replace these outlets? I assume I need to get some bare copper or green insulated wire and connect it to the outlet ground screw on one end and connect it to the metal Jbox via installing another screw above the "GR" label on the junction box in my photo?



Edit:
Attempting to summarize info in multiple answers. It seems my options for properly wiring the new receptacles require me to update the grounding of the box shown in the left photo, where the ground conductors are currently tied around the cable clamp screw in the middle. Google searches tell me that used to be an approved bonding method but is no longer allowed.



To properly ground the jbox and receptacle I can:
A) Terminate a pigtail on the box ground screw hole (will require a 10-32 green ground screw), terminate a pigtail on the receptacle ground screw and tie the 2 pigtails and 2 ground conductors together with a wire nut.



B) Terminate a longer pigtail on the box ground screw hole (will require a 10-32 green ground screw), connect it to the 2 ground conductors in the box with a Greenie wire nut and terminate the other end of the pigtail (which extends through the small hole of the Greenie) on the receptacle ground screw.



In either case do I also need to match my pigtail wire gauge to my 2 ground conductors coming into the box?










share|improve this question




























    3















    Replacing several 3 prong outlets in my 1968 home. Tried searching to find an answer but most questions seem geared towards replacing 2 prong outlets with 3 prong and don't apply here.



    My wiring appears to be romex with a bare copper ground wire. After removing the outlet covers and pulling the outlets (all 3 prong) out of their junction boxes, I've found that each has the hot and neutral wires connected to the outlet and the ground wire connected to the junction box. Each outlet has a black screw in the bottom corner which I assume makes contact with the metal box and provides a ground path?



    Outlet Example



    What is the correct way to replace these outlets? I assume I need to get some bare copper or green insulated wire and connect it to the outlet ground screw on one end and connect it to the metal Jbox via installing another screw above the "GR" label on the junction box in my photo?



    Edit:
    Attempting to summarize info in multiple answers. It seems my options for properly wiring the new receptacles require me to update the grounding of the box shown in the left photo, where the ground conductors are currently tied around the cable clamp screw in the middle. Google searches tell me that used to be an approved bonding method but is no longer allowed.



    To properly ground the jbox and receptacle I can:
    A) Terminate a pigtail on the box ground screw hole (will require a 10-32 green ground screw), terminate a pigtail on the receptacle ground screw and tie the 2 pigtails and 2 ground conductors together with a wire nut.



    B) Terminate a longer pigtail on the box ground screw hole (will require a 10-32 green ground screw), connect it to the 2 ground conductors in the box with a Greenie wire nut and terminate the other end of the pigtail (which extends through the small hole of the Greenie) on the receptacle ground screw.



    In either case do I also need to match my pigtail wire gauge to my 2 ground conductors coming into the box?










    share|improve this question


























      3












      3








      3








      Replacing several 3 prong outlets in my 1968 home. Tried searching to find an answer but most questions seem geared towards replacing 2 prong outlets with 3 prong and don't apply here.



      My wiring appears to be romex with a bare copper ground wire. After removing the outlet covers and pulling the outlets (all 3 prong) out of their junction boxes, I've found that each has the hot and neutral wires connected to the outlet and the ground wire connected to the junction box. Each outlet has a black screw in the bottom corner which I assume makes contact with the metal box and provides a ground path?



      Outlet Example



      What is the correct way to replace these outlets? I assume I need to get some bare copper or green insulated wire and connect it to the outlet ground screw on one end and connect it to the metal Jbox via installing another screw above the "GR" label on the junction box in my photo?



      Edit:
      Attempting to summarize info in multiple answers. It seems my options for properly wiring the new receptacles require me to update the grounding of the box shown in the left photo, where the ground conductors are currently tied around the cable clamp screw in the middle. Google searches tell me that used to be an approved bonding method but is no longer allowed.



      To properly ground the jbox and receptacle I can:
      A) Terminate a pigtail on the box ground screw hole (will require a 10-32 green ground screw), terminate a pigtail on the receptacle ground screw and tie the 2 pigtails and 2 ground conductors together with a wire nut.



      B) Terminate a longer pigtail on the box ground screw hole (will require a 10-32 green ground screw), connect it to the 2 ground conductors in the box with a Greenie wire nut and terminate the other end of the pigtail (which extends through the small hole of the Greenie) on the receptacle ground screw.



      In either case do I also need to match my pigtail wire gauge to my 2 ground conductors coming into the box?










      share|improve this question
















      Replacing several 3 prong outlets in my 1968 home. Tried searching to find an answer but most questions seem geared towards replacing 2 prong outlets with 3 prong and don't apply here.



      My wiring appears to be romex with a bare copper ground wire. After removing the outlet covers and pulling the outlets (all 3 prong) out of their junction boxes, I've found that each has the hot and neutral wires connected to the outlet and the ground wire connected to the junction box. Each outlet has a black screw in the bottom corner which I assume makes contact with the metal box and provides a ground path?



      Outlet Example



      What is the correct way to replace these outlets? I assume I need to get some bare copper or green insulated wire and connect it to the outlet ground screw on one end and connect it to the metal Jbox via installing another screw above the "GR" label on the junction box in my photo?



      Edit:
      Attempting to summarize info in multiple answers. It seems my options for properly wiring the new receptacles require me to update the grounding of the box shown in the left photo, where the ground conductors are currently tied around the cable clamp screw in the middle. Google searches tell me that used to be an approved bonding method but is no longer allowed.



      To properly ground the jbox and receptacle I can:
      A) Terminate a pigtail on the box ground screw hole (will require a 10-32 green ground screw), terminate a pigtail on the receptacle ground screw and tie the 2 pigtails and 2 ground conductors together with a wire nut.



      B) Terminate a longer pigtail on the box ground screw hole (will require a 10-32 green ground screw), connect it to the 2 ground conductors in the box with a Greenie wire nut and terminate the other end of the pigtail (which extends through the small hole of the Greenie) on the receptacle ground screw.



      In either case do I also need to match my pigtail wire gauge to my 2 ground conductors coming into the box?







      wiring receptacle grounding-and-bonding






      share|improve this question















      share|improve this question













      share|improve this question




      share|improve this question








      edited Jan 27 at 3:49







      Aaron Wagner

















      asked Jan 25 at 15:09









      Aaron WagnerAaron Wagner

      163




      163




















          3 Answers
          3






          active

          oldest

          votes


















          2














          The ground screws do not make contact with the box. They're intended to secure a pigtail from the ground wire bundle (or a passthrough loop). On modern outlets they'll be green.



          Some outlets are self-grounding. They have small tabs or wire springs behind the screw mount ears that make a positive connection.



          You can either replace your outlets with self-grounding ones, or simply attach the grounding conductor with the screws. The ground wires should still connect to the box if it's metal. That does appear to be a grounding screw hole in your photo. Be sure to use the proper screw (often 10-32 with self-cutting threads) to be legal.






          share|improve this answer


















          • 1





            I agree but the ground wires in the box need to be anchored also for the contact type yokes to do there job, usually a 10-32 green grounding screw.

            – Ed Beal
            Jan 25 at 15:22











          • Thanks. I was looking up the thread pitch as you commented. 'Preciate the confirmation.

            – isherwood
            Jan 25 at 15:24











          • I am always cautious with grounding screw wording, I believe code states self forming, this is to keep people from using self tappers , but you added the pitch so I think it is worth a +

            – Ed Beal
            Jan 25 at 15:31











          • @EdBeal the issue with sheet metal screws is the thread pitch, not the self-tapping functionality. A 10-32 self-tapper (or even a 10-32 self-driller) is legal under Code, and is even made in green (ask your supply house for a Garvin Industries GSST).

            – ThreePhaseEel
            Jan 27 at 14:06


















          2














          You see on the old receptacle, where there is a little cardboard donut and a bunch of wallpaper and junk stuck to the receptacle yoke? That. That is a picture postcard example of not an acceptable grounding path for receptacles. Those things are insulators, and will prevent solid contact between the yoke and the metal box. Also, the yoke is catching the dry wall and is "proud" of the box. Because of that, it needs a ground pigtail.



          The mounting screws, alone, are not an acceptable grounding path for receptacles. They are for switches. (Why?? shrug)



          The ground screw was not having casual contact with the box sides. The ground wires were, that was grounding the box. The yoke was grouhding through the mounting screws. The screws conduct well enough to pass a 3-lamp test, but they won't handle serious current when they need to. Obviously neither will the "casual contact" of the ground wires to the box.



          If you are changing receptacles, pause to learn what a "tab" is, why you break off "tabs", and check every receptacle for that. You'll thank us later.



          There in the box, that hole is threaded #10-32. Code requires -32 or finer threads for proper thread engagement given the thickness of junction boxes. Do not use any random wood or metal screw. Home Depot sells adorable green screws just for this purpose, some with little ground wires already on them.






          share|improve this answer


















          • 1





            Appreciate all the info. It appears I will also need to add steel extensions to each junction box so that they are flush with the face of my drywall if any of them are recessed more than 1/4 inch? I took another look after you mentioned the yoke being proud of the box and found them to be between 1/4 inch and 3/8 inch each.

            – Aaron Wagner
            Jan 27 at 3:25


















          0














          Yes if that hole indicated in your photo is threaded, that is for the ground screw, and the screw at the bottom of the receptacle is for the ground wire.



          In this situation I think a "greenie" grounding wire nut, a wire nut with a hole in the tip, might be the easiest thing to use.



          Take a 12" pigtail of bare #14 and terminate one end under the ground screw at the back of the box. Run the pigtail through the wire nut and twist the two existing ground wires into the ground screw. Then land the other end of the pigtail on the ground screw terminal on the receptacle.






          share|improve this answer


















          • 1





            The key is the wire-nut and other ground wires joins the ground pigtail at half staff...

            – Harper
            Jan 25 at 15:50










          Your Answer








          StackExchange.ready(function()
          var channelOptions =
          tags: "".split(" "),
          id: "73"
          ;
          initTagRenderer("".split(" "), "".split(" "), channelOptions);

          StackExchange.using("externalEditor", function()
          // Have to fire editor after snippets, if snippets enabled
          if (StackExchange.settings.snippets.snippetsEnabled)
          StackExchange.using("snippets", function()
          createEditor();
          );

          else
          createEditor();

          );

          function createEditor()
          StackExchange.prepareEditor(
          heartbeatType: 'answer',
          autoActivateHeartbeat: false,
          convertImagesToLinks: false,
          noModals: true,
          showLowRepImageUploadWarning: true,
          reputationToPostImages: null,
          bindNavPrevention: true,
          postfix: "",
          imageUploader:
          brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
          contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
          allowUrls: true
          ,
          noCode: true, onDemand: true,
          discardSelector: ".discard-answer"
          ,immediatelyShowMarkdownHelp:true
          );



          );













          draft saved

          draft discarded


















          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f155837%2freplacing-grounded-outlets-with-grounded-metal-junction-box%23new-answer', 'question_page');

          );

          Post as a guest















          Required, but never shown

























          3 Answers
          3






          active

          oldest

          votes








          3 Answers
          3






          active

          oldest

          votes









          active

          oldest

          votes






          active

          oldest

          votes









          2














          The ground screws do not make contact with the box. They're intended to secure a pigtail from the ground wire bundle (or a passthrough loop). On modern outlets they'll be green.



          Some outlets are self-grounding. They have small tabs or wire springs behind the screw mount ears that make a positive connection.



          You can either replace your outlets with self-grounding ones, or simply attach the grounding conductor with the screws. The ground wires should still connect to the box if it's metal. That does appear to be a grounding screw hole in your photo. Be sure to use the proper screw (often 10-32 with self-cutting threads) to be legal.






          share|improve this answer


















          • 1





            I agree but the ground wires in the box need to be anchored also for the contact type yokes to do there job, usually a 10-32 green grounding screw.

            – Ed Beal
            Jan 25 at 15:22











          • Thanks. I was looking up the thread pitch as you commented. 'Preciate the confirmation.

            – isherwood
            Jan 25 at 15:24











          • I am always cautious with grounding screw wording, I believe code states self forming, this is to keep people from using self tappers , but you added the pitch so I think it is worth a +

            – Ed Beal
            Jan 25 at 15:31











          • @EdBeal the issue with sheet metal screws is the thread pitch, not the self-tapping functionality. A 10-32 self-tapper (or even a 10-32 self-driller) is legal under Code, and is even made in green (ask your supply house for a Garvin Industries GSST).

            – ThreePhaseEel
            Jan 27 at 14:06















          2














          The ground screws do not make contact with the box. They're intended to secure a pigtail from the ground wire bundle (or a passthrough loop). On modern outlets they'll be green.



          Some outlets are self-grounding. They have small tabs or wire springs behind the screw mount ears that make a positive connection.



          You can either replace your outlets with self-grounding ones, or simply attach the grounding conductor with the screws. The ground wires should still connect to the box if it's metal. That does appear to be a grounding screw hole in your photo. Be sure to use the proper screw (often 10-32 with self-cutting threads) to be legal.






          share|improve this answer


















          • 1





            I agree but the ground wires in the box need to be anchored also for the contact type yokes to do there job, usually a 10-32 green grounding screw.

            – Ed Beal
            Jan 25 at 15:22











          • Thanks. I was looking up the thread pitch as you commented. 'Preciate the confirmation.

            – isherwood
            Jan 25 at 15:24











          • I am always cautious with grounding screw wording, I believe code states self forming, this is to keep people from using self tappers , but you added the pitch so I think it is worth a +

            – Ed Beal
            Jan 25 at 15:31











          • @EdBeal the issue with sheet metal screws is the thread pitch, not the self-tapping functionality. A 10-32 self-tapper (or even a 10-32 self-driller) is legal under Code, and is even made in green (ask your supply house for a Garvin Industries GSST).

            – ThreePhaseEel
            Jan 27 at 14:06













          2












          2








          2







          The ground screws do not make contact with the box. They're intended to secure a pigtail from the ground wire bundle (or a passthrough loop). On modern outlets they'll be green.



          Some outlets are self-grounding. They have small tabs or wire springs behind the screw mount ears that make a positive connection.



          You can either replace your outlets with self-grounding ones, or simply attach the grounding conductor with the screws. The ground wires should still connect to the box if it's metal. That does appear to be a grounding screw hole in your photo. Be sure to use the proper screw (often 10-32 with self-cutting threads) to be legal.






          share|improve this answer













          The ground screws do not make contact with the box. They're intended to secure a pigtail from the ground wire bundle (or a passthrough loop). On modern outlets they'll be green.



          Some outlets are self-grounding. They have small tabs or wire springs behind the screw mount ears that make a positive connection.



          You can either replace your outlets with self-grounding ones, or simply attach the grounding conductor with the screws. The ground wires should still connect to the box if it's metal. That does appear to be a grounding screw hole in your photo. Be sure to use the proper screw (often 10-32 with self-cutting threads) to be legal.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered Jan 25 at 15:18









          isherwoodisherwood

          47.7k456122




          47.7k456122







          • 1





            I agree but the ground wires in the box need to be anchored also for the contact type yokes to do there job, usually a 10-32 green grounding screw.

            – Ed Beal
            Jan 25 at 15:22











          • Thanks. I was looking up the thread pitch as you commented. 'Preciate the confirmation.

            – isherwood
            Jan 25 at 15:24











          • I am always cautious with grounding screw wording, I believe code states self forming, this is to keep people from using self tappers , but you added the pitch so I think it is worth a +

            – Ed Beal
            Jan 25 at 15:31











          • @EdBeal the issue with sheet metal screws is the thread pitch, not the self-tapping functionality. A 10-32 self-tapper (or even a 10-32 self-driller) is legal under Code, and is even made in green (ask your supply house for a Garvin Industries GSST).

            – ThreePhaseEel
            Jan 27 at 14:06












          • 1





            I agree but the ground wires in the box need to be anchored also for the contact type yokes to do there job, usually a 10-32 green grounding screw.

            – Ed Beal
            Jan 25 at 15:22











          • Thanks. I was looking up the thread pitch as you commented. 'Preciate the confirmation.

            – isherwood
            Jan 25 at 15:24











          • I am always cautious with grounding screw wording, I believe code states self forming, this is to keep people from using self tappers , but you added the pitch so I think it is worth a +

            – Ed Beal
            Jan 25 at 15:31











          • @EdBeal the issue with sheet metal screws is the thread pitch, not the self-tapping functionality. A 10-32 self-tapper (or even a 10-32 self-driller) is legal under Code, and is even made in green (ask your supply house for a Garvin Industries GSST).

            – ThreePhaseEel
            Jan 27 at 14:06







          1




          1





          I agree but the ground wires in the box need to be anchored also for the contact type yokes to do there job, usually a 10-32 green grounding screw.

          – Ed Beal
          Jan 25 at 15:22





          I agree but the ground wires in the box need to be anchored also for the contact type yokes to do there job, usually a 10-32 green grounding screw.

          – Ed Beal
          Jan 25 at 15:22













          Thanks. I was looking up the thread pitch as you commented. 'Preciate the confirmation.

          – isherwood
          Jan 25 at 15:24





          Thanks. I was looking up the thread pitch as you commented. 'Preciate the confirmation.

          – isherwood
          Jan 25 at 15:24













          I am always cautious with grounding screw wording, I believe code states self forming, this is to keep people from using self tappers , but you added the pitch so I think it is worth a +

          – Ed Beal
          Jan 25 at 15:31





          I am always cautious with grounding screw wording, I believe code states self forming, this is to keep people from using self tappers , but you added the pitch so I think it is worth a +

          – Ed Beal
          Jan 25 at 15:31













          @EdBeal the issue with sheet metal screws is the thread pitch, not the self-tapping functionality. A 10-32 self-tapper (or even a 10-32 self-driller) is legal under Code, and is even made in green (ask your supply house for a Garvin Industries GSST).

          – ThreePhaseEel
          Jan 27 at 14:06





          @EdBeal the issue with sheet metal screws is the thread pitch, not the self-tapping functionality. A 10-32 self-tapper (or even a 10-32 self-driller) is legal under Code, and is even made in green (ask your supply house for a Garvin Industries GSST).

          – ThreePhaseEel
          Jan 27 at 14:06













          2














          You see on the old receptacle, where there is a little cardboard donut and a bunch of wallpaper and junk stuck to the receptacle yoke? That. That is a picture postcard example of not an acceptable grounding path for receptacles. Those things are insulators, and will prevent solid contact between the yoke and the metal box. Also, the yoke is catching the dry wall and is "proud" of the box. Because of that, it needs a ground pigtail.



          The mounting screws, alone, are not an acceptable grounding path for receptacles. They are for switches. (Why?? shrug)



          The ground screw was not having casual contact with the box sides. The ground wires were, that was grounding the box. The yoke was grouhding through the mounting screws. The screws conduct well enough to pass a 3-lamp test, but they won't handle serious current when they need to. Obviously neither will the "casual contact" of the ground wires to the box.



          If you are changing receptacles, pause to learn what a "tab" is, why you break off "tabs", and check every receptacle for that. You'll thank us later.



          There in the box, that hole is threaded #10-32. Code requires -32 or finer threads for proper thread engagement given the thickness of junction boxes. Do not use any random wood or metal screw. Home Depot sells adorable green screws just for this purpose, some with little ground wires already on them.






          share|improve this answer


















          • 1





            Appreciate all the info. It appears I will also need to add steel extensions to each junction box so that they are flush with the face of my drywall if any of them are recessed more than 1/4 inch? I took another look after you mentioned the yoke being proud of the box and found them to be between 1/4 inch and 3/8 inch each.

            – Aaron Wagner
            Jan 27 at 3:25















          2














          You see on the old receptacle, where there is a little cardboard donut and a bunch of wallpaper and junk stuck to the receptacle yoke? That. That is a picture postcard example of not an acceptable grounding path for receptacles. Those things are insulators, and will prevent solid contact between the yoke and the metal box. Also, the yoke is catching the dry wall and is "proud" of the box. Because of that, it needs a ground pigtail.



          The mounting screws, alone, are not an acceptable grounding path for receptacles. They are for switches. (Why?? shrug)



          The ground screw was not having casual contact with the box sides. The ground wires were, that was grounding the box. The yoke was grouhding through the mounting screws. The screws conduct well enough to pass a 3-lamp test, but they won't handle serious current when they need to. Obviously neither will the "casual contact" of the ground wires to the box.



          If you are changing receptacles, pause to learn what a "tab" is, why you break off "tabs", and check every receptacle for that. You'll thank us later.



          There in the box, that hole is threaded #10-32. Code requires -32 or finer threads for proper thread engagement given the thickness of junction boxes. Do not use any random wood or metal screw. Home Depot sells adorable green screws just for this purpose, some with little ground wires already on them.






          share|improve this answer


















          • 1





            Appreciate all the info. It appears I will also need to add steel extensions to each junction box so that they are flush with the face of my drywall if any of them are recessed more than 1/4 inch? I took another look after you mentioned the yoke being proud of the box and found them to be between 1/4 inch and 3/8 inch each.

            – Aaron Wagner
            Jan 27 at 3:25













          2












          2








          2







          You see on the old receptacle, where there is a little cardboard donut and a bunch of wallpaper and junk stuck to the receptacle yoke? That. That is a picture postcard example of not an acceptable grounding path for receptacles. Those things are insulators, and will prevent solid contact between the yoke and the metal box. Also, the yoke is catching the dry wall and is "proud" of the box. Because of that, it needs a ground pigtail.



          The mounting screws, alone, are not an acceptable grounding path for receptacles. They are for switches. (Why?? shrug)



          The ground screw was not having casual contact with the box sides. The ground wires were, that was grounding the box. The yoke was grouhding through the mounting screws. The screws conduct well enough to pass a 3-lamp test, but they won't handle serious current when they need to. Obviously neither will the "casual contact" of the ground wires to the box.



          If you are changing receptacles, pause to learn what a "tab" is, why you break off "tabs", and check every receptacle for that. You'll thank us later.



          There in the box, that hole is threaded #10-32. Code requires -32 or finer threads for proper thread engagement given the thickness of junction boxes. Do not use any random wood or metal screw. Home Depot sells adorable green screws just for this purpose, some with little ground wires already on them.






          share|improve this answer













          You see on the old receptacle, where there is a little cardboard donut and a bunch of wallpaper and junk stuck to the receptacle yoke? That. That is a picture postcard example of not an acceptable grounding path for receptacles. Those things are insulators, and will prevent solid contact between the yoke and the metal box. Also, the yoke is catching the dry wall and is "proud" of the box. Because of that, it needs a ground pigtail.



          The mounting screws, alone, are not an acceptable grounding path for receptacles. They are for switches. (Why?? shrug)



          The ground screw was not having casual contact with the box sides. The ground wires were, that was grounding the box. The yoke was grouhding through the mounting screws. The screws conduct well enough to pass a 3-lamp test, but they won't handle serious current when they need to. Obviously neither will the "casual contact" of the ground wires to the box.



          If you are changing receptacles, pause to learn what a "tab" is, why you break off "tabs", and check every receptacle for that. You'll thank us later.



          There in the box, that hole is threaded #10-32. Code requires -32 or finer threads for proper thread engagement given the thickness of junction boxes. Do not use any random wood or metal screw. Home Depot sells adorable green screws just for this purpose, some with little ground wires already on them.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered Jan 25 at 16:04









          HarperHarper

          70.1k447141




          70.1k447141







          • 1





            Appreciate all the info. It appears I will also need to add steel extensions to each junction box so that they are flush with the face of my drywall if any of them are recessed more than 1/4 inch? I took another look after you mentioned the yoke being proud of the box and found them to be between 1/4 inch and 3/8 inch each.

            – Aaron Wagner
            Jan 27 at 3:25












          • 1





            Appreciate all the info. It appears I will also need to add steel extensions to each junction box so that they are flush with the face of my drywall if any of them are recessed more than 1/4 inch? I took another look after you mentioned the yoke being proud of the box and found them to be between 1/4 inch and 3/8 inch each.

            – Aaron Wagner
            Jan 27 at 3:25







          1




          1





          Appreciate all the info. It appears I will also need to add steel extensions to each junction box so that they are flush with the face of my drywall if any of them are recessed more than 1/4 inch? I took another look after you mentioned the yoke being proud of the box and found them to be between 1/4 inch and 3/8 inch each.

          – Aaron Wagner
          Jan 27 at 3:25





          Appreciate all the info. It appears I will also need to add steel extensions to each junction box so that they are flush with the face of my drywall if any of them are recessed more than 1/4 inch? I took another look after you mentioned the yoke being proud of the box and found them to be between 1/4 inch and 3/8 inch each.

          – Aaron Wagner
          Jan 27 at 3:25











          0














          Yes if that hole indicated in your photo is threaded, that is for the ground screw, and the screw at the bottom of the receptacle is for the ground wire.



          In this situation I think a "greenie" grounding wire nut, a wire nut with a hole in the tip, might be the easiest thing to use.



          Take a 12" pigtail of bare #14 and terminate one end under the ground screw at the back of the box. Run the pigtail through the wire nut and twist the two existing ground wires into the ground screw. Then land the other end of the pigtail on the ground screw terminal on the receptacle.






          share|improve this answer


















          • 1





            The key is the wire-nut and other ground wires joins the ground pigtail at half staff...

            – Harper
            Jan 25 at 15:50















          0














          Yes if that hole indicated in your photo is threaded, that is for the ground screw, and the screw at the bottom of the receptacle is for the ground wire.



          In this situation I think a "greenie" grounding wire nut, a wire nut with a hole in the tip, might be the easiest thing to use.



          Take a 12" pigtail of bare #14 and terminate one end under the ground screw at the back of the box. Run the pigtail through the wire nut and twist the two existing ground wires into the ground screw. Then land the other end of the pigtail on the ground screw terminal on the receptacle.






          share|improve this answer


















          • 1





            The key is the wire-nut and other ground wires joins the ground pigtail at half staff...

            – Harper
            Jan 25 at 15:50













          0












          0








          0







          Yes if that hole indicated in your photo is threaded, that is for the ground screw, and the screw at the bottom of the receptacle is for the ground wire.



          In this situation I think a "greenie" grounding wire nut, a wire nut with a hole in the tip, might be the easiest thing to use.



          Take a 12" pigtail of bare #14 and terminate one end under the ground screw at the back of the box. Run the pigtail through the wire nut and twist the two existing ground wires into the ground screw. Then land the other end of the pigtail on the ground screw terminal on the receptacle.






          share|improve this answer













          Yes if that hole indicated in your photo is threaded, that is for the ground screw, and the screw at the bottom of the receptacle is for the ground wire.



          In this situation I think a "greenie" grounding wire nut, a wire nut with a hole in the tip, might be the easiest thing to use.



          Take a 12" pigtail of bare #14 and terminate one end under the ground screw at the back of the box. Run the pigtail through the wire nut and twist the two existing ground wires into the ground screw. Then land the other end of the pigtail on the ground screw terminal on the receptacle.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered Jan 25 at 15:24









          batsplatstersonbatsplatsterson

          11.7k11536




          11.7k11536







          • 1





            The key is the wire-nut and other ground wires joins the ground pigtail at half staff...

            – Harper
            Jan 25 at 15:50












          • 1





            The key is the wire-nut and other ground wires joins the ground pigtail at half staff...

            – Harper
            Jan 25 at 15:50







          1




          1





          The key is the wire-nut and other ground wires joins the ground pigtail at half staff...

          – Harper
          Jan 25 at 15:50





          The key is the wire-nut and other ground wires joins the ground pigtail at half staff...

          – Harper
          Jan 25 at 15:50

















          draft saved

          draft discarded
















































          Thanks for contributing an answer to Home Improvement Stack Exchange!


          • Please be sure to answer the question. Provide details and share your research!

          But avoid


          • Asking for help, clarification, or responding to other answers.

          • Making statements based on opinion; back them up with references or personal experience.

          To learn more, see our tips on writing great answers.




          draft saved


          draft discarded














          StackExchange.ready(
          function ()
          StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f155837%2freplacing-grounded-outlets-with-grounded-metal-junction-box%23new-answer', 'question_page');

          );

          Post as a guest















          Required, but never shown





















































          Required, but never shown














          Required, but never shown












          Required, but never shown







          Required, but never shown

































          Required, but never shown














          Required, but never shown












          Required, but never shown







          Required, but never shown






          Popular posts from this blog

          How to check contact read email or not when send email to Individual?

          Displaying single band from multi-band raster using QGIS

          How many registers does an x86_64 CPU actually have?